本文已被:浏览次 下载次 |
码上扫一扫! |
|
|
Optimal placement of harmonic measurement unit based on ant-algorithm for distribution network |
WANG Yan-song, SUN Gui-long
|
(College of Information and Control Engineering in China University of Petroleum, Qingdao 266580, China)
|
Abstract: |
An optimal placement of the harmonic measurement can effectively improve the feasibility and accuracy of the harmonic state estimation for a distribution network. The principle of placing the distribution network harmonic measuring unit is determined based on the characteristics of the distribution network. Using distribution network topology, a mathematical model is derived to calculate the node-voltage-state observability. The PMU optimal placement of the mathematical model is established with comprehensive considerations of the node-voltage-state observability degree and redundancy. Ant-algorithm is proposed to solve the optimal placement problem of the harmonic measuring unit, which can give a variety of schemes to meet the same optimization goal for the planning, and can be designed to choose the optimal solution according to the real situations. The results show that the ant-algorithm is effective for the optimal placement of the harmonic measurement. The redundancy of nodes is effectively reduced and the number of observable nodes is sufficiently increased by the optimal placement of the PMU. |
Key words: distribution network ant-algorithm phasor measurement unit(PMU) observability degree redundancy |
|